Load Cell Scale Transmitter
2026-02-27T19:53:49+00:00

Scale Calibration

Add known weight points to calibrate the scale
83.0 lb
STABLE

📋 How to Calibrate

  1. Start empty - Remove all weight from the scale
  2. Add 0 lb point - Enter 0 in the field below and click "Add Point"
  3. Add known weights - Place a known weight on the scale, wait for STABLE, enter the weight and click "Add Point"
  4. Repeat - Add 3-5 points across your operating range for best accuracy

Add Calibration Point

Point will be captured with current signal value. Scale must be STABLE. Average mode requires confirmation.

Saved Calibration Points 9

# Weight (lb) Signal Time Action
1 3.0 5.644000 16:53:33
2 25.0 5.840429 16:53:33
3 50.0 6.063643 16:53:33
4 100.0 6.510071 16:53:33
5 150.0 6.956500 16:53:33
6 200.0 7.402929 16:53:33
7 250.0 7.849357 16:53:33
8 300.0 8.295786 16:53:33
9 335.0 8.608286 16:53:33

PLC Output Mapping

Nudge the Pi output until the PLC display matches the scale weight
Active Port: 0_10V on Channel 2
To change the port or mode, go to the Settings page.
Runtime Mapping: No PLC profile — add mapping points below
Train the PLC output at known weights to build the mapping curve.
✓ OUTPUTS ARMED
⚠️ WARNING: Channel is shared with another function
0.000 V

Saved Output Mapping (0-10V)

Weight (lb) Output (V) Action
10.0 0.190 V
25.0 0.340 V
50.0 0.590 V
75.0 0.840 V
100.0 1.090 V
125.0 1.340 V
150.0 1.590 V
175.0 1.840 V
200.0 2.090 V
225.0 2.340 V
250.0 2.590 V
275.0 2.840 V
300.0 3.090 V
325.0 3.340 V
350.0 3.590 V
375.0 3.840 V
400.0 4.090 V